The 30 ft throw cannot reach the floor area inside the office unless the hose nozzle reaches the door.
Standpipe 30 ft access to roof.
Class iii standpipe systems shall be installed throughout buildings where the floor level of the highest story is located more than 30 feet 9144 mm above the lowest level of fire department vehicle access or where the floor level of the lowest story is located more than 30 feet 9144 mm below the highest level of fire department vehicle access.
In buildings four or more stories or more than 40 feet 12 192 mm in height above grade one stairway shall extend to the roof surface through a stairway bulkhead complying with section 1509 2 unless the roof has a slope steeper than 20 degrees 0 35 rad access to setback roof areas may be through a door or window opening to the roof.
With a standpipe system installed in a building the fire fighter can connect hose to a permanently installed valve on the standpipe system and with not more than 100 to 200 ft 35 5 m to 61 m of hose can fight a fire anywhere on a given floor.
The code specifically states in f 905 3 1 height.
3 more than 50 ft 15 m above grade and containing intermediate stories or balconies 4 more than one story below grade 5 more than 20 ft 6 1 m below grade in addition standpipes are required in high rise buildings and some stage areas in assembly occupancies.
If that is the case the ahj could reasonable accept ignoring the walls since they know that application of the 100 ft plus 30 ft throw provides spacing well within the ability.
The international fire code states that a class iii standpipe system shall be installed throughout buildings where the floor level of the highest story is located more than 30 feet above the lowest level of fire department access or where the floor level of the lowest story is located more than 30 feet below the highest level of fire department access.
Standpipe systems are divided into classes to identify their specific function.
It requires a class iii standpipe be installed throughout buildings where the floor level of the highest story is located more than 30 ft above the lowest level of fire department access or where the lowest floor level is located more than 30 ft below the highest level of fire department vehicle access.
Stairs terminating at the level of a setback shall.